A test report of the type appropriate to the equipment tested shall be drawn up for
each test in conformity with one or other of the models 1 to 12 hereunder.
MODEL No. 1 A
Method used 1, 3 ......................... Figures used 1, 3...........................
MODEL No. 1 A (cont’d)
MODEL No. 1 B
MODEL No. 1 B (cont’d)
MODEL No. 2 A
Portion of power absorbed by the fans entering the body: W2 ................W
MODEL No. 2 A (cont’d)
Expanded uncertainty with test used ... % (coverage factor k = ... for an accepted
confidence level ........................ %)3
Remarks4/......................................................................................
______________________________________________________________________
(To be completed only if the equipment does not have thermal appliances:)
According to the above test results, the equipment may be recognized by means of a
certificate in accordance with ATP annex 1, appendix 3, valid for a period of not
more than six years, with the distinguishing mark IN/IR1/.
However, this report shall be valid as a certificate of type approval within the meaning
of ATP annex 1, appendix 1, paragraph 6 (a) only for a period of not more than six
years, that is until
...................................................................................
Done at: ......
|
|
Date of test report ......
|
|
|
Testing Officer
|
1/ Delete as necessary.
2/ For inside-cooling test only.
3 The present provisions concerning the use of expanded uncertainty instead of the
maximum error are applicable to the tests carried out after 1 January 2021
4/ If the body is not parallelepipedic, specify the points at which the outside and
inside temperatures were measured
MODEL No. 2 B
Portion of power absorbed by the fans entering the body: W2 ................W
MODEL No. 2 B (cont’d)
Expanded uncertainty with test used ... % (coverage factor °C = ... for an accepted
confidence level ........................ %)3
Remarks1/......................................................................................
______________________________________________________________________
(To be completed only if the equipment does not have thermal appliances:)
According to the above test results, the equipment may be recognized by means of a
certificate in accordance with ATP annex 1, appendix 3, valid for a period of not
more than six years, with the distinguishing mark IN/IR1/.
However, this report shall be valid as a certificate of type approval within the meaning
of ATP annex 1, appendix 1, paragraph 6 (a) only for a period of not more than six
years, that is until
...................................................................................
Done at: ......
|
|
Date of test report ......
|
|
|
Testing Officer
|
1/ If the tank is not parallelepipedic, specify the points at which the outside and
inside temperatures were measured.
2/ Delete as necessary.
3 The present provisions concerning the use of expanded uncertainty instead of the
maximum error are applicable to the tests carried out after 1 January 2021
MODEL No. 3
Done at: ......
|
|
Date of test report ......
|
|
|
Testing Officer
|
1/ Delete as necessary.
MODEL No. 4 A
MODEL No. 4 A (cont’d)
Done at: ......
|
|
Date of test report ......
|
|
|
Testing Officer
|
MODEL No. 4 B
MODEL No. 4 B (cont’d)
MODEL No. 4 B (cont’d)
Done at: ......
|
|
Date of test report ......
|
|
|
Testing Officer
|
MODEL No. 4 C
MODEL No. 4 C (cont’d)
Done at: ......
|
|
Date of test report ......
|
|
|
Testing Officer
|
MODEL No. 5
Drive: electric/thermal/hydraulic/other1/
MODEL No. 5 (cont’d)
MODEL No. 5 (cont’d)
Done at: ......
|
|
Date of test report ......
|
|
|
Testing Officer
|
MODEL No. 6
MODEL No. 6 (cont’d)
Done at: ......
|
|
Date of test report ......
|
|
|
Testing Officer
|
2/ Increased by 35% for new equipment.
MODEL No. 7
Drive: electric/thermal/hydraulic/other1/
MODEL No 7 (cont'd)
Done at: ......
|
|
Date of test report ......
|
|
|
Testing Officer
|
1 Delete if not applicable.
2 Only for cooling appliances.
3 Increased by 35% for new equipment.
4 Only for heating appliances.
MODEL No. 8
MODEL No. 8(cont’d)
Done at: ......
|
|
Date of test report ......
|
|
|
Testing Officer
|
MODEL No. 9
MODEL No. 9 (cont’d)
Done at: ......
|
|
Date of test report ......
|
|
|
Testing Officer
|
MODEL No. 10
MODEL No. 10 (cont’d)
Done at: ......
|
|
Date of test report ......
|
|
|
Testing Officer
|
According to the above test results, this report shall be valid as a certificate of
type approval within the meaning of ATP Annex 1, Appendix 1, paragraph 6 (a) only for a period of not more than six years, that is until: ................................................
---------------------------------------------------------------------------------------------------------------------------------------------------------------------
According to the above test results, the equipment may be recognized by means of a
certificate in accordance with ATP annex 1, appendix 3, valid for a period of not more than three years, with the distinguishing mark .............................................
MODEL No. 11
MODEL No. 11 (cont'd)
Done at: ......
|
|
Date of test report ......
|
|
|
Testing Officer
|
MODEL No. 12
|
|
TEST REPORT
|
|
|
|
|
|
|
Prepared in conformity with the provisions of the Agreement on the International Carriage
of Perishable Foodstuffs and on the Special Equipment to be Used for such Carriage
(ATP)
|
|
|
|
|
|
|
Test Report No.....
|
|
|
|
|
|
|
Determination of the effective refrigerating capacity of a refrigeration unit in accordance
with section 4 of ATP Annex 1, Appendix 2
|
|
|
Date of testing from DD/MM/YYYY to DD/MM/YYYY
|
|
|
|
|
(Reference document: ECE/TRANS/WP.11/2016/2 as amended)
|
Methods of drive1/: electric motor, seperate internal combostion engine, vehicle engine, vehicle motion,
other
MODEL No. 12 (cont’d)
Other: …
Speed of rotation
|
(nominal speed given by the manufacturer:
(
(.........................rpm
(
(minimum speed: ..................rpm
|
Refrigerant charge....................................
Refrigerant fluid: (ISO/ASHRAE designation)a) ............................................................
Nominal mass of refrigerant ............................................................................................
a) If existing
|
Heat exchangers
|
Condensor
|
Evaporator
|
Make 2/
|
|
|
Type (if applicable) 2/
|
|
|
Number of tubes
|
|
|
Fan pitch (mm)2/
|
|
|
Tube: nature and diameter (mm)2/
|
|
|
Exchange surface area (m2)2/
|
|
|
Frontal area (m2)
|
|
|
FANS
|
Number
|
|
|
Number of blades per fan
|
|
|
Diameter (mm)
|
|
|
|
Nominal power (W)2/3/
|
|
|
Total nomimal output at a pressure of ..... Pa (m3/h)2
|
|
|
Method of drive
|
|
|
Expansion valve:
|
Make:.......................
|
Model:............
|
|
Adjustable: 1/................
|
Not adjustable: 1/..............
|
Defrosting device:
|
....................
|
Automatic device:
|
....................
|
MODEL No. 12 (cont’d)
MODEL No. 12 (cont’d)
Air flow volume leaving the evaporator:
value measured.........................m3/h
at a static:
-
• differential pressure measured between the air flows leaving and entering the evaporator
of 0 Pa,
-
• absolute barometric air pressure of ...........................hPa.
Model No. 13
TEST REPORT
|
|
Prepared in conformity with the special provisions of the Agreement on the International
Carriage of Perishable Foodstuffs and on the Special Equipment to be used for such
carriage (ATP)
|
|
Test Report No......
|
|
Determination of the effective refrigeration capacity of a refrigeration unit in accordance
with section 9 of ATP Annex 1, Appendix 2
|
|
Tests carried out from mm/dd/yyyy to mm/dd/yyyy
|
Approved testing station
|
Name: ......
|
Adress: ......
|
|
Refrigerating unit presented by: ......
|
[(a declaration by the manufacturer shall be provided if the applicant is not the
manufacturer)]
|
|
(a)
|
Technical specifications of the unit:
|
|
|
|
Make/Brand
|
:
|
|
|
Type designation
|
:
|
|
|
Type of liquefied gas
|
:
|
|
|
Serial number
|
:
|
|
|
|
|
|
Date of manufacture (month/year):(The tested unit shall not have been built more than
1 year prior to ATP tests.)
|
Description:
|
......
|
......
|
......
|
|
|
|
|
Regulating valve (if different types of fans are used repeat information below for
each type)
|
|
Make/Brand
|
:
|
|
|
Type
|
:
|
|
|
Serial number
|
:
|
|
|
|
|
|
Tank (if different types of fans are used repeat information below for each type)
|
|
Make/Brand
|
:
|
|
|
Type
|
:
|
|
|
Serial number
|
:
|
|
|
Capacity [l]
|
:
|
|
|
Gas pressure at tank outlet
|
:
|
|
|
Method of insulation
|
:
|
|
|
Material of inner tank
|
:
|
|
|
Material of outer tank
|
:
|
|
|
Supply of liquefied gas
|
:
|
(internal pressure, pressure by heat exchanger, pump)1
|
|
Pressure regulator
|
|
Make/Brand
|
:
|
|
|
Type
|
:
|
|
|
Serial number
|
:
|
|
|
Gas pressure at pressure outlet
|
:
|
|
|
|
|
|
Supply liquefied gas line (on the test bench)
|
|
Diameter
|
:
|
|
|
Length
|
:
|
|
|
Material
|
:
|
|
|
Number of connections
|
:
|
|
|
|
|
|
Defrosting device (Electric / Combustion unit)1
|
|
Make/Brand
|
:
|
|
|
Type
|
:
|
|
|
Supply
|
:
|
|
|
Declared heating capacity
|
:
|
|
|
|
|
|
Regulator
|
|
Make/Brand
|
:
|
|
|
Type
|
:
|
|
|
Hardware version
|
:
|
|
|
Software version
|
:
|
|
|
Serial number
|
:
|
|
|
Power supply
|
:
|
|
|
|
|
|
Possibility for Multi-temperature operation : (yes/no)1
|
Number of compartments able to work in multi-temperatures:
|
HEAT EXCHANGERS
|
Condenser
|
Evaporator
|
Make-Type
|
|
|
Number of circuits
|
|
|
Number of rows
|
|
|
Number of blankets
|
|
|
Number of tubes
|
|
|
Fin pitch [mm]
|
|
|
Tube : nature and diameter [mm]
|
|
|
Total exchange surface [m2]
|
|
|
Face area [m2]
|
|
|
FANS
|
Make-Type
|
|
|
Number
|
|
|
Blade per fan
|
|
|
Diameter [mm]
|
|
|
Power [W]
|
|
|
Nominal speed [rpm]
|
|
|
Total nominal output airflow [m3/h] at a pressure of 0 Pa
|
|
|
Method of drive
(Description direct current / alternative, frequency, etc.)
|
|
|
(b)
|
Test method and results:
|
|
|
Test method1: Heat balance method/enthalpy difference method
|
|
In a calorimeter box of mean surface area of = ...... m2
|
Measured value of the U-value of the calorimeter box fitted with the liquefied gas
unit: ...... W/°C,
|
|
At a mean wall temperature: ...... °C.
|
|
In a transport equipment
|
|
Measured value of the U-value of the transport equipment fitted with the liquefied
gas unit: ...... W/ °C,
|
|
At a mean wall temperature: ...... °C.
|
|
The formula employed for the correction of the U-value of the calorimeter box as a
function of the mean wall temperature is:
|
......
|
......
|
|
Maximum errors of determination of:
|
U-value of the body: ......
|
|
Refrigerating capacity of the liquefied gas unit: ......
|
Mean air temperature at the tank outside: ...... °C
|
|
Electric power supply: ......
|
Liquefied gas consumption
|
Electrical consumption
|
Pressure at the tank outlet
|
Temperature of the liquid at the evaporator
|
External temperature
|
Internal temperature
|
Heating power
|
Evaporator air intake temperature
|
Useful refrigerating capacity
|
[kg/h]
|
[Vdc] and [A]
|
[bar abs]
|
[°C]
|
[°C]
|
[°C]
|
[W]
|
[°C]
|
[W]
|
|
|
|
|
|
|
|
|
|
Corrected cooling capacity [W]:
|
|
(c)
|
Checks:
|
|
|
Temperature regulator:
|
Setting ...... °C
|
|
Differential ......°C
|
|
Functioning of the defrosting device1: satisfactory / unsatisfactory
|
|
Airflow volume leaving the evaporator:
|
|
|
Value measured: ...... m3/h
|
|
At a pressure of ...... Pa
|
|
At a temperature of ...... °C
|
|
At a rotation speed of ...... tr/min.
|
|
|
Minimum capacity tank: ......
|
|
|
(d)
|
Remarks
|
......
|
......
|
......
|
This test report is valid for a maximum duration of six years after the date of the
end of the tests.
|
|
|
Done at: ......
|
|
|
On: ......
|
Testing officer
|
|
|
|
......
|
1
Delete where applicable.
2
Value indicated by the manufacturer”.
Model No. 14